modbusctl — Modbus Command-Line Tool for TCP, RTU & ASCII: Poll, Write, Scan, Identify, SunSpec, Record & Simulate

Go Version License: MIT CI Status Code Coverage Latest Release

modbusctl is a command-line toolkit for exploring, operating, testing and simulating Modbus devices over TCP, UDP and serial lines (RTU and ASCII). Read, poll and write coils and registers, identify a device, fingerprint which function codes it supports, scan its register map to find readable blocks, decode registers into typed values, discover Modbus devices on a subnet, record sessions to a compact capture file (MCAP) and replay them as a simulated device.

It is built for commissioning and site surveys, troubleshooting, reverse-engineering undocumented register maps, SunSpec inverter and meter discovery, and building hardware-free test setups. Output can be plain text, a table or JSON with stable exit codes, so it works in scripts and CI. It is written in Go on top of go-modbus.

Quick links: Quick start · Comparison · Features · Transports · Scan algorithms · MCAP format · FAQ

Responsible use: modbusctl sends real Modbus requests. Only use it on devices and networks you own or are authorized to test. Some devices react badly to scanning, so start with --algo safe and a --delay. client write changes coils and registers, and FC08 diagnostic sub-functions can change device state (for example restart communications, clear counters or force listen-only mode): know what an address controls before you write to it.


Why modbusctl?

  • Understand an unknown device — identify (FC43/FC17), fingerprint (supported read functions per unit) and client sunspec tell you what you are talking to.
  • Find the register map — scan discovers readable address blocks with seven strategies, from the gentle safe to the adaptive smart and evidence-driven deep.
  • Typed decoding — decode turns registers into integers, floats, strings, BCD, timestamps, IP and MAC addresses with explicit byte and word layouts.
  • Poll and write — poll reads a block at an interval and streams every sample; write sets coils and holding registers, with the same codecs for typed values.
  • Every common transport — Modbus TCP, Modbus UDP, serial RTU and ASCII (RS-232/RS-485), and RTU or ASCII framing through a serial-to-Ethernet bridge, all selected with --url.
  • Record, replay, simulate — Capture sessions to MCAP, then serve them with server static or server replay to develop and test without hardware.
  • Find devices — discover sweeps subnets for Modbus devices, with a safety cap on large ranges.
  • Script-friendly — --format text|json|table, a single JSON error object on failure, stable exit codes and MODBUSCTL_* environment variables.
  • Offline analysis — Convert, decode, extract, summarize and string-search recorded data with the mcap commands.
  • Pre-built binaries — Linux, macOS and Windows (x86-64 and ARM) from GitHub Releases, with SHA-256 checksums; no runtime to install.

Quick start

Download a binary from GitHub Releases (see Installation for copy-paste commands for Linux, macOS and Windows, or build from source), then point it at a device:

# What is this device? (FC43 Device Identification + FC17 Report Server ID)
modbusctl client identify --ip 192.168.1.10 --server-id

# Which read function codes does each unit support?
modbusctl client fingerprint --ip 192.168.1.10 --unit 1-10

# Which register blocks are readable? (adaptive scan, saved to MCAP)
modbusctl client scan --ip 192.168.1.10 --algo smart --start 0 --end 5000 --output scan.mcap

# Read and decode a 32-bit float, as JSON
modbusctl client decode --ip 192.168.1.10 --start 40001 --codec float32/layout:4321 --format json

# Poll four holding registers every second until Ctrl-C
modbusctl client poll --ip 192.168.1.10 --start 100 --count 4

# Write a holding register on a serial RTU device
modbusctl client write --url rtu:///dev/ttyUSB0 --baud 9600 --unit 3 --start 100 --values 1234

# Serve the scan results as a simulated Modbus TCP device on port 1502
modbusctl server static --input scan.mcap --port 1502

SunSpec device? Run modbusctl client sunspec probe --url tcp://192.168.1.10:502 --unit 1.

Addresses are raw Modbus PDU addresses (0–65535), not "4xxxx" register labels. See Read registers.


modbusctl vs mbpoll and modpoll

mbpoll and modpoll are well-known Modbus command-line tools focused on polling and writing registers. modbusctl covers the same ground — polling and writing over TCP, UDP, RTU and ASCII — and adds device exploration, scanning and simulation. This table shows where each tool fits.

Capability modbusctl mbpoll modpoll
Modbus TCP master ✅ ✅ ✅
Modbus RTU (serial) ✅ ✅ ✅
Modbus ASCII and UDP ✅ — ✅
RTU / ASCII framing over TCP (serial bridges) ✅ — ✅
Read coils, discrete inputs, input and holding registers ✅ ✅ ✅
Write coils and holding registers ✅ ✅ ✅
Continuous polling at an interval ✅ ✅ ✅
Typed values (ints, floats, strings, word/byte order) ✅ ✅ ✅
BCD, timestamp, IP and MAC decoders ✅ — —
Register-map scanning (find readable blocks) ✅ — —
Device identification (FC43) and Report Server ID (FC17) ✅ partial (RTU only) —
Diagnostics (FC08 sub-functions) ✅ — —
Supported-function fingerprinting ✅ — —
SunSpec discovery ✅ — —
Subnet device discovery ✅ — —
Record and replay sessions ✅ — —
Simulate a device from recorded data ✅ — —
Export data to CSV / JSON ✅ — CSV
JSON output and stable exit codes for scripting ✅ — —
MQTT publishing — — ✅
Docker image — — ✅
Shell completion ✅ — —
Install release binaries apt, brew, source pip, pipx, Docker
Language / runtime Go C++ (libmodbus) Python 3.10+
License MIT GPL-3.0 MIT

✅ = documented feature · — = not documented / not available. Based on each project's public documentation as of October 2026. If you spot an inaccuracy, please open an issue and we will correct it.

Choose modbusctl if you want one tool to poll and write over TCP, UDP, RTU or ASCII and also explore or map an unfamiliar device, inventory devices, work with SunSpec, capture traffic for analysis, simulate a device from a recording, or script Modbus checks with JSON output.

Choose mbpoll if you want a small, classic poll-and-write tool that is available from your package manager.

Choose modpoll if you want config-file-driven polling with MQTT publishing, or a ready-made Docker setup.

They combine well: use modbusctl to discover and document a device's register map, then feed it into the long-running collector that fits your deployment.


Use cases

  • Commissioning and site surveys — Identify devices, check supported functions, read decoded values and set a coil or setpoint in seconds, on Ethernet or an RS-485 bus.
  • Live monitoring while you work — Poll a few registers at an interval and watch them change, or pipe JSON Lines into a script.
  • Reverse-engineering register maps — Scan for readable blocks, then use mcap strings and mcap frequencies to locate device names and measurements.
  • Hardware-free testing — Record a real device once, then replay it in CI or on a laptop with server replay.
  • Solar and energy equipment — Detect SunSpec markers, walk model chains and print address maps for inverters and meters.
  • Network inventory — Sweep subnets for Modbus TCP devices and export the results as JSON.
  • Automation and CI — Use --format json, exit codes and environment variables in scripts and pipelines.

Table of Contents


Features

The following features are available:

Feature Description
Scan Identify available Modbus register blocks with pluggable algorithms: safe, smart, deep, stepped, linear, boundary, sunspec. See Scan algorithms and ALGOS.md for details.
Identify Read Device Identification (FC43) from a Modbus device.
Fingerprint Probe supported read functions (FC08/FC43/FC03/FC04/FC01/FC02/FC11/FC18/FC20) per unit: functions the device answers or recognises, not ones it rejects as illegal.
Diagnostic Send FC08 Diagnostics requests (loopback, restart communications, diagnostic counters, etc.).
ReportServerID Send FC17 Report Server ID and display server ID, run indicator, and additional device data.
Read Retrieve raw data from specified Modbus registers (arbitrary count, MCAP capture).
Poll Read the same block of coils or registers at an interval and print every sample as it arrives (text, JSON Lines or table), optionally decoded with a codec. Nothing is written to disk.
Write Write coils (FC05/FC15) and holding registers (FC06/FC16). Integer values, or typed values (floats, 32/64-bit integers, strings, …) encoded with a codec.
Transports Modbus TCP, Modbus UDP, serial RTU and ASCII, and RTU or ASCII framing over TCP, selected with --url. See Transports and serial settings.
Decode (registers) Read holding/input registers (FC03/FC04) and decode them into typed values (integers, floats, strings, BCD, time, IP, MAC, …) using a codec such as float32/layout:4321 or ascii/registers:8.
Codecs List available register codecs (id, family, value kind, register/byte width) with optional family / value-kind / register-width filters.
Record Record Modbus responses into structured MCAP files for replay or analysis.
Static Serve previously scanned Modbus data to simulate device behavior (static hosting).
Replay Serve previously recorded Modbus data to simulate device behavior (dynamically updated).
Convert Convert MCAP data into human-readable formats (CSV, JSON).
Decode Decode MCAP data using specific device profiles.
Extract Extract raw data from recorded MCAP files.
Info Display detailed metadata and statistics about MCAP files, including channel information, record counts, and time ranges.
Strings Extract all printable string data from MCAP files for inspection, debugging, or searching for embedded text.
Frequencies Extract potential frequency readings around 50Hz from MCAP files to help finding the correct data ranges
Discovery Discover Modbus devices within specified subnets.
SunSpec Transport-level SunSpec discovery: detect marker/base, enumerate model headers, print address map, or combined probe (no semantic decoding).
Client --format Many modbusctl client commands accept --format text|json|table (or MODBUSCTL_OUTPUT_FORMAT) for structured stdout; mcap convert uses a different --format (csv / json).
Completion Generate shell completion scripts for bash, zsh, fish, or PowerShell; enum flags (--format, --algo, --function, --codec, --regtype, --sub-function, etc.) support tab completion.

The following tree view gives the overview of available commands.

modbusctl
├── client
│   ├── identify         FC43 Read Device Identification (+ optional FC17 Report Server ID)
│   ├── fingerprint      Probe supported read functions per unit
│   ├── diagnostic       FC08 Diagnostics (loopback, counters, restart, …)
│   ├── reportserverid   FC17 Report Server ID
│   ├── read             Read registers (FC01/FC02/FC03/FC04)
│   ├── decode           Read and decode registers into typed values via a codec (FC03/FC04)
│   ├── codecs           List available register codecs for decode, poll and write
│   ├── poll             Poll coils/registers at an interval and print every sample
│   ├── write            Write coils (FC05/FC15) or holding registers (FC06/FC16)
│   ├── scan             Scan for valid register blocks (algo safe|smart|deep|stepped|linear|boundary|sunspec)
│   ├── record           Record registers over time to MCAP
│   └── sunspec           SunSpec marker detection and model header discovery
│       ├── detect       Detect SunSpec marker and base address
│       ├── models       Enumerate SunSpec model headers
│       ├── map          Print SunSpec address map summary
│       └── probe        Combined fingerprint + SunSpec detection summary
├── server
│   ├── static           Serve scanned MCAP data (static)
│   └── replay           Replay recorded MCAP data (dynamic)
├── mcap
│   ├── convert          Convert MCAP → JSON / CSV
│   ├── decode           Decode MCAP with device profiles
│   ├── extract          Extract address blocks from MCAP
│   ├── info             MCAP metadata & statistics
│   ├── strings          Extract printable strings from MCAP
│   └── frequencies      Detect ~50 Hz frequency data in MCAP
├── discover             Discover Modbus devices on subnets
├── completion           Generate shell completion script (bash|zsh|fish|powershell)
└── version              Print version

Installation

The easiest way to install modbusctl is to download a pre-built binary from the GitHub Releases page. No Go toolchain is required.

Platform CPU Download
Linux x86-64 modbusctl-<version>-linux-amd64.tar.gz
Linux 64-bit ARM (Raspberry Pi 4/5 with a 64-bit OS, AWS Graviton) modbusctl-<version>-linux-arm64.tar.gz
Linux 32-bit ARM (Raspberry Pi with a 32-bit OS) modbusctl-<version>-linux-armv7.tar.gz
macOS Apple Silicon (M1 and later) modbusctl-<version>-darwin-arm64.tar.gz
macOS Intel modbusctl-<version>-darwin-amd64.tar.gz
Windows x86-64 modbusctl-<version>-windows-amd64.zip
Windows ARM64 modbusctl-<version>-windows-arm64.zip

Each release also contains modbusctl-<version>-checksums.txt (SHA-256) so you can verify your download. The commands below fetch the latest release, verify its checksum and install it. Afterwards, check that it works:

modbusctl version

Linux

# 1. Find the latest version and your CPU architecture
VERSION=$(curl -fsSLI -o /dev/null -w '%{url_effective}' https://github.com/otfabric/modbusctl/releases/latest | sed 's|.*/v||')
case "$(uname -m)" in
  x86_64)         ARCH=amd64 ;;
  aarch64|arm64)  ARCH=arm64 ;;
  armv7l)         ARCH=armv7 ;;
  *) echo "Unsupported architecture: $(uname -m)" ;;
esac

# 2. Download the archive and the checksum file
FILE="modbusctl-${VERSION}-linux-${ARCH}.tar.gz"
BASE="https://github.com/otfabric/modbusctl/releases/download/v${VERSION}"
curl -fsSLO "${BASE}/${FILE}"
curl -fsSLO "${BASE}/modbusctl-${VERSION}-checksums.txt"

# 3. Verify the download (should print "OK")
grep "${FILE}" "modbusctl-${VERSION}-checksums.txt" | sha256sum -c -

# 4. Extract and install (the binary in the archive carries the version and platform in its name)
mkdir -p modbusctl-dl && tar -xzf "${FILE}" -C modbusctl-dl
sudo install -m 0755 "$(find modbusctl-dl -type f -name 'modbusctl*' | head -n1)" /usr/local/bin/modbusctl

No sudo? Install into your home directory instead (and make sure ~/.local/bin is in your PATH):

mkdir -p ~/.local/bin
install -m 0755 "$(find modbusctl-dl -type f -name 'modbusctl*' | head -n1)" ~/.local/bin/modbusctl

macOS

# 1. Find the latest version and your CPU architecture (arm64 = Apple Silicon, x86_64 = Intel)
VERSION=$(curl -fsSLI -o /dev/null -w '%{url_effective}' https://github.com/otfabric/modbusctl/releases/latest | sed 's|.*/v||')
case "$(uname -m)" in
  arm64)   ARCH=arm64 ;;
  x86_64)  ARCH=amd64 ;;
esac

# 2. Download the archive and the checksum file
FILE="modbusctl-${VERSION}-darwin-${ARCH}.tar.gz"
BASE="https://github.com/otfabric/modbusctl/releases/download/v${VERSION}"
curl -fsSLO "${BASE}/${FILE}"
curl -fsSLO "${BASE}/modbusctl-${VERSION}-checksums.txt"

# 3. Verify the download (should print "OK")
grep "${FILE}" "modbusctl-${VERSION}-checksums.txt" | shasum -a 256 -c -

# 4. Extract and install (the binary in the archive carries the version and platform in its name)
mkdir -p modbusctl-dl && tar -xzf "${FILE}" -C modbusctl-dl
sudo install -m 0755 "$(find modbusctl-dl -type f -name 'modbusctl*' | head -n1)" /usr/local/bin/modbusctl

If you downloaded the archive with a web browser instead of curl and macOS refuses to run the binary ("cannot be verified"), remove the quarantine flag: xattr -d com.apple.quarantine /usr/local/bin/modbusctl.

Windows (PowerShell)

# 1. Find the latest version and your CPU architecture
$version = (Invoke-RestMethod https://api.github.com/repos/otfabric/modbusctl/releases/latest).tag_name.TrimStart('v')
$arch    = if ($env:PROCESSOR_ARCHITECTURE -eq 'ARM64') { 'arm64' } else { 'amd64' }

# 2. Download the archive and the checksum file
$file = "modbusctl-$version-windows-$arch.zip"
$base = "https://github.com/otfabric/modbusctl/releases/download/v$version"
Invoke-WebRequest "$base/$file" -OutFile "$env:TEMP\$file"
Invoke-WebRequest "$base/modbusctl-$version-checksums.txt" -OutFile "$env:TEMP\modbusctl-checksums.txt"

# 3. Verify the download (throws an error on mismatch)
$expected = ((Select-String -Path "$env:TEMP\modbusctl-checksums.txt" -Pattern $file).Line -split '\s+')[0]
$actual   = (Get-FileHash "$env:TEMP\$file" -Algorithm SHA256).Hash
if ($expected -ne $actual) { throw "Checksum mismatch for $file" }

# 4. Extract to a per-user folder and name the program modbusctl.exe
#    (the .exe in the archive carries the version and platform in its name)
$dir = "$env:LOCALAPPDATA\Programs\modbusctl"
New-Item -ItemType Directory -Force -Path $dir | Out-Null
Expand-Archive "$env:TEMP\$file" -DestinationPath "$env:TEMP\modbusctl-dl" -Force
$exe = Get-ChildItem "$env:TEMP\modbusctl-dl" -Recurse -Filter 'modbusctl*.exe' | Select-Object -First 1
Copy-Item $exe.FullName "$dir\modbusctl.exe" -Force

# 5. Add modbusctl to your user PATH (then open a new terminal)
$userPath = [Environment]::GetEnvironmentVariable('Path', 'User')
if ($userPath -notlike "*$dir*") {
  [Environment]::SetEnvironmentVariable('Path', "$userPath;$dir", 'User')
}

If Windows SmartScreen warns about an unrecognised app, choose More info → Run anyway.

Manual download

  1. Open the latest release.
  2. Download the archive for your platform from the table above.
  3. Extract it, rename the binary to modbusctl (modbusctl.exe on Windows) and move it to a folder on your PATH.

Update

Run the same commands again. They always fetch the latest release and overwrite the previous binary.

Build from source

Requires Go 1.25 or later:

git clone https://github.com/otfabric/modbusctl.git
cd modbusctl
make build

make build writes the binary to bin/modbusctl (see Building).


MCAP Format

The MCAP (Modbus Capture) format is a specialized binary format designed for efficiently recording and replaying Modbus TCP communications, inspired by the well-known PCAP (Packet Capture) format used by tools such as Wireshark.

Why MCAP?

MCAP provides a structured, compact, and efficient way to store Modbus data for:

  • Recording Modbus interactions with timestamps, iteration counters, and metadata.
  • Replaying recorded data for testing or simulation of Modbus devices.
  • Analyzing and decoding Modbus registers for debugging and diagnostics.

MCAP File Structure

An MCAP file contains two main components, each encoded for a specific purpose:

Component Description
Header Includes metadata such as IP address, port, function codes, timestamps, and protocol-specific details. The header is JSON encoded for readability and easy inspection.
Records Sequential Modbus transaction records containing iteration counts, precise request and response timestamps, register addresses, counts, and raw data payloads. The records are binary encoded for performance and compactness, enabling efficient storage and fast replay.

The following is an example of a JSON converted MCAP file:

{
  "header": {
    "ip": "192.168.2.201",
    "port": 502,
    "unit": 21,
    "function": 3,
    "start_time": "2025-07-14T13:05:56.998694708Z"
  },
  "records": [
    {
      "iteration": 0,
      "request_timestamp": "2025-07-14T13:14:24.701149758Z",
      "response_timestamp": "2025-07-14T13:14:24.951906811Z",
      "start_address": 4096,
      "register_count": 62,
      "raw_data": "000001a7000000f3000000f4000000f5000001a4000001a8000001a8ffffffff0000013f000001ab000001cf00000047000001cdffffffa0ffffffd1ffffffffffffffffffffffffffffffff000001270000004e00000068000000720000001400000024fffffff6fffffffbfffffee9ffffffbeffffff9bffffff90"
    },
    {
      "iteration": 1,
      "request_timestamp": "2025-07-14T13:14:31.312332629Z",
      "response_timestamp": "2025-07-14T13:14:31.570347588Z",
      "start_address": 4158,
      "register_count": 67,
      "raw_data": "000003b40000a790ffffffffffffffff0000c36effffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffffff"
    }
  ]
}

More examples and test files can be found in the results folder for quick exploration and verification.


Usage

General CLI Usage

Global flag: --debug — print debug information (available for all commands; per-command debug behavior is documented where applicable).

Client address: All client commands accept either --url (e.g. tcp://192.168.1.10:502 or rtu:///dev/ttyUSB0) or --ip and optionally --port (Modbus TCP); the two styles are mutually exclusive (you must set one and cannot set both). See Transports and serial settings.

Client stdout format (--format): Commands identify, read, decode, write, poll, scan, record, reportserverid, fingerprint, diagnostic, and client sunspec (detect, models, map, probe) accept --format text (default), json, or table, or set MODBUSCTL_OUTPUT_FORMAT. This controls only the final human- or machine-readable result on stdout. It is not the same as modbusctl mcap convert --format, which chooses csv or json export for MCAP files (env MODBUSCTL_FORMAT).

Scan and record: Live progress (scan lines, per-block lines, worst-case hints, --debug traces, record iteration messages) goes to stderr; stdout is a single formatted result after the run (summary for scan/record). When using --format json, redirect or separate streams if scripts must not mix progress with JSON.

Fatal errors: With --format json, client commands write a single JSON error object to stdout on failure (fields kind, code, message) and use stable exit codes. With text or table, fatals use a single error: line on stderr and leave stdout empty. See docs/exitcodes.md for the exit-code table. Per-unit failures in JSON success payloads use a structured error object (kind, code, message) on each affected row where applicable (identify, reportserverid, fingerprint).

modbusctl [command] [flags]

modbusctl client identify
modbusctl client fingerprint
modbusctl client diagnostic
modbusctl client reportserverid
modbusctl client read
modbusctl client decode
modbusctl client codecs
modbusctl client poll
modbusctl client write
modbusctl client scan
modbusctl client record
modbusctl client sunspec detect
modbusctl client sunspec models
modbusctl client sunspec map
modbusctl client sunspec probe

modbusctl server static
modbusctl server replay

modbusctl mcap convert
modbusctl mcap decode
modbusctl mcap extract
modbusctl mcap info
modbusctl mcap strings
modbusctl mcap frequencies

modbusctl discover
modbusctl version

Shell completion: Enum-style flags support tab completion, including --format (client: text/json/table; mcap convert: csv/json), --algo, --function, --codec, --parity, --regtype, and --sub-function. To enable completion, generate and source the script (see Cobra’s shell completion guide); for example, modbusctl completion bash (or zsh / fish / powershell).

Transports and serial settings

Every modbusctl client command talks to the device named by --url. The scheme selects the transport:

URL Transport
tcp://host:port Modbus TCP (same as --ip host --port port)
udp://host:port Modbus TCP framing over UDP
rtu://<device> Modbus RTU on a serial line (RS-232 / RS-485)
ascii://<device> Modbus ASCII on a serial line
rtuovertcp://host:port RTU framing over TCP (serial-to-Ethernet bridge)
rtuoverudp://host:port RTU framing over UDP
asciiovertcp://host:port ASCII framing over TCP (serial-to-Ethernet bridge)

<device> is the serial port: rtu:///dev/ttyUSB0 on Linux, rtu:///dev/cu.usbserial-1420 on macOS, rtu://COM3 on Windows.

The serial line is configured with four flags, available on every client command and ignored for network URLs:

Flag Values Default
--baud any rate the adapter supports 19200
--data-bits 5, 6, 7, 8 8 for rtu://, 7 for ascii://
--parity none, even, odd none
--stop-bits 1, 2 2 without parity, 1 with parity
# RTU at 9600 8E1, unit 3
modbusctl client read --url rtu:///dev/ttyUSB0 --baud 9600 --parity even --unit 3 --start 0 --count 4

# ASCII at 9600 7E1
modbusctl client identify --url ascii:///dev/ttyUSB0 --baud 9600 --parity even --unit 1

# Modbus UDP
modbusctl client decode --url udp://192.168.1.10:502 --start 100 --codec uint32/layout:4321

# An RTU device behind a serial-to-Ethernet bridge
modbusctl client scan --url rtuovertcp://192.168.1.50:4001 --unit 7 --start 0 --end 200 --output scan.mcap

Good to know:

  • Defaults differ between tools. Many devices ship as 9600 8N1; the Modbus specification default is 19200 8E1. If a serial device does not answer, check --baud, --parity and --stop-bits against its manual first.
  • One request at a time on a serial line. With rtu:// and ascii://, --parallel is ignored and units are queried one after the other.
  • Unit IDs matter on a bus. A unit that is not present does not answer, so each missing unit costs one --timeout. Use a short timeout (for example --timeout 300) when sweeping units with --unit 1-32.
  • MCAP captures made over a serial line store the device path in the header's ip field and port 0.
  • server and discover are Modbus TCP only.
  • UDP transports are not part of the Modbus specification; vendors use either udp:// (MBAP framing) or rtuoverudp://. Try both if unsure.

Common Commands

Read Device Identification (FC43)

By default the command requests all categories (basic + regular + extended). You can restrict to one or more categories with optional flags. Use --unit to target a single unit, a range, a list, or all units (1–255). Use --server-id to additionally query FC17 Report Server ID.

Unit selection (--unit):

Value Meaning Example
N Single unit ID --unit 1
N-M Range (inclusive) --unit 1-10
N,M,P Comma-separated list --unit 1,5,25
N-M,P,... Mix of range(s) and list --unit 1-10,255
all All units 1–255 --unit all

When probing multiple units, use --parallel N (default 10) to run probes concurrently. Use --format json or --format table for machine-readable or tabular output.

# All categories (default), single unit
modbusctl client identify --ip 192.168.1.10

# Also retrieve FC17 Report Server ID data
modbusctl client identify --ip 192.168.1.10 --server-id

# Specific category or combine --basic, --regular, --extended
modbusctl client identify --ip 192.168.1.10 --basic
modbusctl client identify --ip 192.168.1.10 --basic --regular

# Unit: single, range, list, or all (with optional --parallel for multiple units)
modbusctl client identify --ip 192.168.1.10 --unit 1
modbusctl client identify --ip 192.168.1.10 --unit 1-10
modbusctl client identify --ip 192.168.1.10 --unit 1,5,25
modbusctl client identify --ip 192.168.1.10 --unit all
modbusctl client identify --ip 192.168.1.10 --unit all --parallel 10

Category flags (optional):

Flag Category Objects included
(none) All Basic + Regular + Extended (single request)
--basic Basic VendorName, ProductCode, MajorMinorRevision
--regular Regular Basic + VendorUrl, ProductName, ModelName, UserApplicationName
--extended Extended Regular + vendor-specific objects (0x80–0xFF)
--server-id FC17 Server ID, run indicator status, additional data

Example result (object names are looked up when known; reserved/extended IDs are labelled):

🔍 Connecting to 192.168.1.10:502...
✅ Device Identification (DevID Code: 1, Conformity Level: 0x01, More Follows: 0x00, Next Object ID: 0, Object Count: 6)
 - Object 0: HUAWEI [VendorName]
 - Object 1: Smart Logger [ProductCode]
 - Object 2: V200R002C20SPC121 [MajorMinorRevision]
 - Object 3: [VendorUrl]
  FC17 Report Server ID (byte count: 5): 01 FF 48 55 41

Fingerprint Device (fingerprint)

Probe each requested unit with one request per read-style function code (FC08, FC43, FC03, FC04, FC01, FC02, FC11, FC18, FC20), using go-modbus SupportsFunction. Output is the list of supported read functions per unit. Use --interval (ms) to add a delay between probes to avoid overloading the device.

A function counts as supported when the unit answers it normally, or with an exception that shows it recognised the function (for example Illegal Data Address for a register that does not exist). Illegal Function, a gateway exception for a unit that is not there, and no answer at all count as not supported.

# Fingerprint unit 1 (default)
modbusctl client fingerprint --ip 192.168.1.10

# Add delay between probes (e.g. 100 ms)
modbusctl client fingerprint --ip 192.168.1.10 --unit 1 --interval 100

# Fingerprint a range or all units
modbusctl client fingerprint --ip 192.168.1.10 --unit 1-10
modbusctl client fingerprint --ip 192.168.1.10 --unit all

Example output:

🔍 Fingerprinting device at 192.168.1.10:502 (supported read functions per unit)...

--- Unit ID 1 ---
✅ Unit 1: supported read functions:
  Read Holding Registers (0x03)
  Read Input Registers (0x04)
  Diagnostics (0x08)
  Report Server ID (0x11)
  Read Device Identification (0x2B)

Diagnostics (FC08)

Send an FC08 Diagnostics request. Use --sub-function with the sub-function name (lowercase, e.g. returnquerydata, clearcountersanddiagnosticreg). Default is returnquerydata (loopback). Tab completion is available for --sub-function.

FC08 sub-function names and codes
CLI name (--sub-function) Code
returnquerydata 0x0000
restartcommunications 0x0001
returndiagnosticregister 0x0002
changeasciiinputdelimiter 0x0003
forcelistenonlymode 0x0004
clearcountersanddiagnosticreg 0x000A
returnbusmessagecount 0x000B
returnbuscommunicationerrorcount 0x000C
returnbusexceptionerrorcount 0x000D
returnservermessagecount 0x000E
returnservernoresponsecount 0x000F
returnservernakcount 0x0010
returnserverbusycount 0x0011
returnbuscharacteroverruncount 0x0012
clearoverruncounterandflag 0x0014
# Loopback test (default: returnquerydata, data 0000)
modbusctl client diagnostic --ip 192.168.1.10

# Loopback with custom data
modbusctl client diagnostic --ip 192.168.1.10 --data A537

# Return Bus Message Count
modbusctl client diagnostic --ip 192.168.1.10 --sub-function returnbusmessagecount

# Specific unit
modbusctl client diagnostic --ip 192.168.1.10 --unit 5 --sub-function returnquerydata

Example output:

🔍 Sending FC08 Diagnostics to 192.168.1.10:502 (unit 1, sub-function returnquerydata / 0x0000)...
✅ Diagnostics response:
  Sub-function: 0x0000 (ReturnQueryData)
  Data:         00 00

Report Server ID (FC17)

Send an FC17 Report Server ID request. Returns the server ID byte, run indicator status (ON/OFF), and any additional device-specific data.

# Query server ID from unit 1
modbusctl client reportserverid --ip 192.168.1.10

# Query a range of units
modbusctl client reportserverid --ip 192.168.1.10 --unit 1-10

# Query all units in parallel
modbusctl client reportserverid --ip 192.168.1.10 --unit all --parallel 10

Example output (default --format text):

🔍 Sending FC17 Report Server ID to tcp://192.168.1.10:502...
✅ Report Server ID (unit 1):
  Data: 01 FF 48 55 41
  Run Indicator: ON

Read registers (single or block)

Use --format for stdout (after any MCAP write). --output still writes MCAP when set.

Addresses: --start, scan --start/--end, and record block JSON use raw Modbus PDU addresses (16-bit values as on the wire: 0–65535). They are not “4xxxx minus 40001” style logical labels — e.g. --start 40001 is literal address 40001, not “register 1”.

modbusctl client read --ip 192.168.1.10 --start 30001 --count 2
modbusctl client read --ip 192.168.1.10 --start 40001 --count 10 --output data.mcap
modbusctl client read --ip 192.168.1.10 --start 40001 --count 10 --format json

Note: read is the raw-capture command (arbitrary register count, MCAP output). Typed interpretation of register values now lives in client decode. The former --ascii and --byteswap flags have been removed; use the corresponding codecs instead (e.g. --codec ascii/registers:N, or a layout-aware numeric codec such as uint32/layout:2143).

Decode registers (typed values via codecs)

client decode reads holding (FC3) or input (FC4) registers and decodes them into typed values using a go-modbus codec. The codec determines how many registers each value spans. Omit --count to decode a single value; set --count to a multiple of the codec register width to decode an array of values. Run modbusctl client codecs to list every available codec ID.

modbusctl client decode --ip 192.168.1.10 --start 40001 --codec float32/layout:4321
modbusctl client decode --ip 192.168.1.10 --function 4 --start 0 --codec ascii/registers:8
modbusctl client decode --ip 192.168.1.10 --start 100 --codec uint32/layout:4321 --count 8 --format json
modbusctl client decode --ip 192.168.1.10 --start 200 --codec ip_addr

List codecs

modbusctl client codecs
modbusctl client codecs --family float
modbusctl client codecs --registers 2 --format table
modbusctl client codecs --value-kind string --format json

Poll registers continuously

client poll reads the same block every --interval milliseconds and prints each sample as soon as it is read. It does not write a file; use client record to capture to MCAP.

It runs until --polls samples were taken, or until you press Ctrl-C when --polls is 0 (the default). --function selects coils (1), discrete inputs (2), holding registers (3, default) or input registers (4). With --codec, registers are decoded into typed values exactly as client decode does.

# Four holding registers, once a second, until Ctrl-C
modbusctl client poll --ip 192.168.1.10 --start 100 --count 4

# A big-endian float32 from input registers, every 500 ms, 20 times
modbusctl client poll --ip 192.168.1.10 --function 4 --start 0 --codec float32/layout:4321 --interval 500 --polls 20

# Eight coils as JSON Lines
modbusctl client poll --ip 192.168.1.10 --function 1 --start 0 --count 8 --format json

# A serial RTU device
modbusctl client poll --url rtu:///dev/ttyUSB0 --baud 9600 --unit 3 --start 0 --count 2

Samples go to stdout, one per poll; a one-line summary goes to stderr when polling ends:

# --format text (default): timestamp, poll number, address=value
2026-10-09T12:00:00.004Z  #1  100=1234 101=0 102=0 103=0
2026-10-09T12:00:01.004Z  #2  100=1235 101=0 102=0 103=0

# --format json: one object per line
{"poll":1,"timestamp":"2026-10-09T12:00:00.004Z","unit_id":1,"function":3,"start_address":200,"count":2,"address_step":2,"codec":"float32/layout:4321","rtt_ms":0.4,"raw_data_hex":"41 AC 00 00","values":[21.5]}

# --format table: header once, then one row per poll
poll      timestamp                 rtt_ms    8         9         10        11        error
-         -                         -         -         -         -         -         -
1         2026-10-09T12:00:00.004Z  0.4       1         0         1         1

# stderr, at the end
2 poll(s) of tcp://192.168.1.10:502 in 1.004s: 2 succeeded, 0 failed

A poll that fails — timeout, Modbus exception, lost connection — is printed as a sample with an error (error object in JSON) and polling continues, reconnecting when needed. The exit code is 0 when every poll succeeded and 7 (partial) when at least one failed; stopping with Ctrl-C is not an error. Polls start on a fixed cadence: if a read takes longer than --interval, the next one starts immediately.

Write coils and registers

client write writes coils (FC05, FC15) or holding registers (FC06, FC16). --values takes one value or a comma-separated list, written to consecutive addresses starting at --start.

--function Writes Values
(omitted) holding registers: FC06 for one register, FC16 for several integers, or typed values with --codec
6 one holding register one integer
16 1–123 holding registers integers, or typed values with --codec
5 one coil 1/0, true/false, on/off
15 1–1968 coils list of coil values

Register values are 0–65535, 0x-prefixed hex, or -32768–-1 (written as two's complement). With --codec, each value is encoded into as many registers as the codec needs, so floats, 32/64-bit integers, strings, IP addresses and timestamps can be written directly; modbusctl client codecs lists the codec IDs.

# One holding register (FC06)
modbusctl client write --ip 192.168.1.10 --start 100 --values 1234

# Three holding registers (FC16)
modbusctl client write --ip 192.168.1.10 --start 100 --values 10,0x00FF,-1

# Switch coil 8 on (FC05)
modbusctl client write --ip 192.168.1.10 --function 5 --start 8 --values on

# Four coils (FC15)
modbusctl client write --ip 192.168.1.10 --function 15 --start 8 --values 1,0,1,1

# A big-endian float32 setpoint: two registers, FC16
modbusctl client write --ip 192.168.1.10 --start 200 --codec float32/layout:4321 --values 21.5

# Modbus RTU on a serial line
modbusctl client write --url rtu:///dev/ttyUSB0 --baud 9600 --parity even --unit 3 --start 100 --values 1234
Writing 3 register(s) starting at address 100 using function code 16
  [100] 10 (0x000A)
  [101] 255 (0x00FF)
  [102] 65535 (0xFFFF)
✅ Wrote 3 register(s) to unit 1

Safeguards:

  • --start is required. There is no default address for a write.
  • Everything is validated before anything is sent — values, codec, quantity limits and the address range. A rejected command (exit code 3) has sent nothing.
  • A write is sent exactly once. It is never retried, because a retry after a lost response could apply the write twice. If a write times out, read the value back before sending it again.
  • A Modbus exception from the device (for example Illegal Data Address for a read-only register) is reported as an error with exit code 6.

Scan registers (discover valid address blocks)

Scan discovers which register ranges are readable and writes successful reads to an MCAP file. Choose the algorithm with --algo:

Algorithm Description Use case
safe Conservative linear probing with descending block sizes (125, 64, 32, 16, 8, 4, 2, 1). Tries largest first; on failure tries smaller; on full failure advances by one address. Optional one-off left-boundary probe after success following failures. Fixed delay, no retry storms. Fragile devices, first pass, production.
smart Adaptive interval splitting with a priority queue (smaller intervals first; tie-break by start). Starts with 125-register chunks, splits failed intervals in half until count 1. Efficient on sparse maps, discovers boundaries sooner. Unknown devices, best default.
deep Runs smart first, then evidence-driven refinement: only where a failed interval is adjacent to a successful one, probes ±8 registers around that edge with counts [1, 2, 4, 8]. Cap 500 refinement tasks. Lab work, reverse engineering, difficult devices.
stepped Quick check at step positions (e.g. 0, 1000, 2000). At each step probes 6 reads (pos−1, pos, pos+1 × count 1 or 2); on any hit expands with 125,64,32,16,8,4 strictly within --start/--end. Use --step (default 1000) and optional --step-half-offset for step/2 positions. Fast discovery of hotspots; full range with few reads when no hits.
linear 125-aligned blocks: probe 125 at a time; on success extend forward, then binary-search for max tail. When a 125 succeeds after a previous 125 failed, binary-search backwards for the real start. Emits a single gap probe between blocks to detect small islands. Longest continuous blocks with minimal probes; good when registers are mostly contiguous.
boundary Given a known-good read (--seed-start, --seed-count), expands left/right with exponential then binary search; clamps to --start/--end (no skip). Invalid or out-of-range seed → no tasks. One known-good range; find maximal readable interval around it.
sunspec SunSpec protocol-aware: probes candidate base addresses for the SunS marker, then walks the model chain — reads each header (2 regs) followed by the full model body (in chunks of ≤125 regs). No --start/--end needed. Use --sunspec-base to skip detection; --sunspec-bases for custom candidates; --sunspec-max-models / --sunspec-max-span for limits. SunSpec-compliant devices; full model capture to MCAP.

Flags: --ip (required), --start, --end, --function (3=holding, 4=input), --delay (ms between requests), --algo (safe | smart | deep | stepped | linear | boundary | sunspec), --step (stepped algo only, default 1000), --step-half-offset (stepped: also probe at step/2), --retry-timeout (0 or 1: retry once on timeout/transport error), --seed-start and --seed-count (boundary algo: known-good read), --sunspec-base (sunspec: known base, skip detection), --sunspec-bases (sunspec: custom candidate bases), --sunspec-max-models (sunspec: max headers, 0=256), --sunspec-max-span (sunspec: max address span, 0=unlimited), --output (MCAP file), --format (stdout summary: text | json | table). Use global --debug to print each read range (start, count, end) on stderr before attempting. Default algo is safe.

# Safe (default): conservative, low device load
modbusctl client scan --ip 192.168.1.10 --start 0 --end 1000 --output scan.mcap

# Smart: interval splitting, good for sparse maps
modbusctl client scan --ip 192.168.1.10 --algo smart --start 0 --end 5000 --output scan.mcap

# Deep: smart + boundary refinement for hard devices
modbusctl client scan --ip 192.168.1.10 --algo deep --function 3 --start 0 --end 2000 --output scan.mcap

# With delay between requests (e.g. 100 ms)
modbusctl client scan --ip 192.168.1.10 --start 1 --end 65535 --delay 100 --output scan-results.mcap

# Input registers (function code 4)
modbusctl client scan --ip 192.168.1.10 --function 4 --algo smart --output input_scan.mcap

# Stepped: quick check every 1000 registers (override with --step 100, 2000, 10000, etc.)
modbusctl client scan --ip 192.168.1.10 --algo stepped --step 1000 --output scan.mcap
modbusctl client scan --ip 192.168.1.10 --algo stepped --step 2000 --start 0 --end 20000 --output scan.mcap

# Linear: 125-aligned blocks, extend forward then tail; backward to find real start after late hit
modbusctl client scan --ip 192.168.1.10 --algo linear --start 0 --end 5000 --output scan.mcap

# Boundary: expand from a known-good read (e.g. from a prior scan or stepped hit)
modbusctl client scan --ip 192.168.1.10 --algo boundary --seed-start 100 --seed-count 10 --start 0 --end 500 --output scan.mcap

# With global --debug: print each read range, result outcome, and strategy internals (phase, state, decisions) for all algos
modbusctl client scan --ip 192.168.1.10 --algo safe --delay 10 --output scan.mcap --debug

# SunSpec: auto-detect base address and walk model chain
modbusctl client scan --ip 192.168.1.10 --algo sunspec --output sunspec.mcap

# SunSpec: known base address (skip detection)
modbusctl client scan --ip 192.168.1.10 --algo sunspec --sunspec-base 40000 --output sunspec.mcap

# SunSpec: custom candidate bases
modbusctl client scan --ip 192.168.1.10 --algo sunspec --sunspec-bases "0,40000,50000" --output sunspec.mcap

For every algorithm, a one-line worst-case hint and all live progress (scanning banner, each Block: line, --debug traces) go to stderr. Stdout prints one final summary after the run (default text, or json / table via --format). The summary includes algorithm, total requests, success/failed counts, exception/timeout/transport error breakdown (when non-zero), blocks and registers captured, average response time, duration, and output path.

# stderr (illustrative)
Scanning registers from 0 to 1000 with function code 3 (algo: smart)
Block: Start: 0, End: 124, Count: 125
Block: Start: 250, End: 311, Count: 62

# stdout (default text)
Algo: smart
Requests: 418
Success: 91
Failed: 327
Blocks captured: 91
Registers captured: 1842
Avg response time: 12 ms
Duration: 2m14s
Output: scan.mcap

When non-zero, the summary also reports Exception, Timeout, and Transport error counts (from outcome classification) so you can distinguish Modbus exceptions from transient failures.

Scan algorithms (detailed)
Algo When to use
safe Fragile device; small range; predictable, conservative scan.
smart Best default. Unknown device; medium/large range; efficient discovery.
deep After smart; you want precise interval edges (evidence-driven refinement).
stepped Huge range; cheap triage; quick reconnaissance (not a final mapper).
linear Long contiguous maps; PLC-style devices; fast when fragmentation is low.
boundary You have one known-good (start, count); find maximal readable interval around it.
sunspec SunSpec device; protocol-aware base detection + model chain walk to MCAP.

Failures are classified (success, Modbus exception, timeout, transport error) so strategies can avoid retrying on strong exception evidence (e.g. Illegal Data Address). For a full specification of each algorithm (state, transitions, worst-case counts, and examples suitable for re-implementation), see ALGOS.md. For the optional improvement roadmap (priority queue, stepped offsets, coalesce-smart, etc.), see REFACTOR.md.

Scan algorithm internals (full descriptions of each algorithm)
  • safe — Linear scan from --start to --end. At each address the scanner tries the largest allowed block first (up to 125 registers), then smaller sizes in a fixed descending order (125, 64, 32, 16, 8, 4, 2, 1). On success it records the block and jumps past it; if there were failures at this address before success, it emits one left-boundary probe (start−1, 1) to help find the exact edge (one-off; does not alter scan position). On total failure it advances by one register. No retry storms. If --start > --end, the strategy is done immediately. Best when you want predictable load and full coverage.

  • smart — Divide-and-conquer over the same range using a priority queue (smaller intervals first; tie-break by start address). It starts with aligned 125-register chunks. If a chunk read fails and the chunk is larger than one register, it splits that chunk in half and re-queues both halves; if it succeeds, the chunk is recorded and not split further. This discovers readable regions and boundaries efficiently without sliding one address at a time. Best default for unknown devices.

  • deep — Two phases. Phase 1 runs the same interval discovery as smart. Phase 2 refines only where there is evidence of a boundary: a failed interval whose range intersects the edge (e.g. [edge−1, edge+1]). It then probes ±8 registers around those edges with counts [1, 2, 4, 8], capped at 500 tasks. Use for difficult devices or when you need precise interval edges.

  • stepped — Optimized for a quick pass over a large range. Step positions are start, start+step, … up to end (--step, default 1000). With --step-half-offset, it also adds positions at start+step/2, start+step+step/2, etc. (deduplicated, sorted). At each step it runs 6 probes: read 1 and 2 registers at pos−1, pos, pos+1 (probe addresses may extend ±1 at range edges for boundary detection). If any probe succeeds it “expands” from that address with 125, 64, 32, 16, 8, 4; expansion reads are strictly within --start/--end. If none of the 6 probes succeed it moves to the next step. Worst case (no hits): steps × 6; the tool prints this at the start.

  • linear — Finds maximum continuous blocks using 125-register reads. It probes 125-aligned blocks; on success extends forward then binary-searches for the maximum tail; when a 125 succeeds after a previous 125 failed it binary-searches backwards for the real start. When there is a gap between the end of one block and the next 125-block, it emits one (blockEnd, 1) gap probe to detect small readable islands (result is recorded but does not change probe/forward/backward state). Worst case with no hits: one read per 125-block in range.

  • boundary — Starts from a known-good read (--seed-start, --seed-count). Expands left and right with exponential sizes (1, 2, 4, 8, 16, 32, 64, 125), then binary-searches for exact boundaries. Clamps to --start/--end (never skips a size). If the seed does not overlap the configured range or is invalid, the strategy is done immediately and emits no tasks. Use when you have one known-good address and want the maximal readable interval around it.

  • sunspec — SunSpec protocol-aware scan. Phase 1 probes candidate base addresses (default: 0, 40000, 50000, …) for the SunS marker (0x5375, 0x6E53). Phase 2 walks the model chain: reads each header (2 regs for model ID + length), then reads the full model body in chunks of ≤125 registers, until the end model (0xFFFF, 0), a read failure, or a configured limit (--sunspec-max-models, --sunspec-max-span). When --sunspec-base is set, detection is skipped. Does not require --start/--end. Worst case: B base probes + M × (1 + ⌈length/125⌉) reads. Use for SunSpec-compliant inverters, meters, and energy devices.

Record registers over time (interval, duration based)

Progress messages (e.g. each iteration and recorded block) go to stderr; stdout is a single final summary (--format text|json|table).

modbusctl client record --ip 192.168.1.10 --blocks-file register-ranges.json --interval 1000 --duration 60000 --output session.mcap
modbusctl client record --ip 192.168.1.10 --blocks-file register-ranges.json --interval 1000 --duration 60000 --output session.mcap --format json

Statically host data (no changes in data)

modbusctl server static --input session.mcap --port 1502

Replay recorded data (looped)

modbusctl server replay --input session.mcap --port 1502 --loops 0
modbusctl server replay --input session.mcap --loops=0 --interval=1000

Convert data to json or csv

modbusctl mcap convert --input session.mcap --format json --output data.json
modbusctl mcap convert --input session.mcap --format csv --output data.csv

Decode data using device profiles (decoding+scaling)

modbusctl mcap decode --input data.mcap --profile device_profile.json --output output.json

Extract data address blocks (continuous readable address spaces)

modbusctl mcap extract --input input.mcap --output register-ranges.json

Information data (meta data, timing statistics)

modbusctl mcap info --input data.mcap --output info.txt

Search for strings data (device identification)

Extracts printable ASCII strings from MCAP data. The command tries four common byte/register layouts (ABCD, BADC, CDAB, DCBA) automatically and tags each hit with the layout that produced it (e.g. [ABCD] [100-103] 4 regs: TEST). No byte-order flag is needed.

modbusctl mcap strings --input file.mcap --output strings.txt
modbusctl mcap strings --input file.mcap

Search for frequency data (data discovery)

modbusctl mcap frequencies --input file.mcap --output frequencies.txt

Discover devices (nmap alike probing)

Large subnets are capped by default (unique host count); use --force-large-scan (or MODBUSCTL_DISCOVER_FORCE_LARGE) when you intentionally want to probe beyond that safety limit.

modbusctl discover --subnets 192.168.1.0/24 --output discovered.json
sudo modbusctl discover --subnets 192.168.1.0/24,192.168.2.0/24 --resolve-mac --interface eth1 --output discovered.json

SunSpec (client sunspec)

Transport-level SunSpec discovery: detect the SunSpec "SunS" marker, enumerate model headers, print the address map, or run a combined probe. Use --url (e.g. tcp://192.168.1.10:502) or --ip/--port; --unit (0–255, full Modbus range); --regtype holding or input (tab-completed). No semantic decoding of points—only marker and model ID/length.

Command Description
detect Is the unit SunSpec? Shows base address; use --bases 0,40000,50000 to probe specific bases, --verbose for attempt log, --format json for JSON.
models Enumerate the SunSpec model chain (start/end address, model ID, length, end model). Use --base to skip detection when base is known; --max-models, --max-address-span to limit reads; --format json for JSON.
map Human-friendly address map (marker regs + model ranges). Options: --show-header-regs, --show-next, --compact, --format json.
probe One-shot summary: Modbus FC03/FC04/FC43 support plus SunSpec detection (base, model count, end model). Complements fingerprint and identify.
# Detect SunSpec and show base address
modbusctl client sunspec detect --url tcp://192.168.1.10:502 --unit 1
modbusctl client sunspec detect --ip 192.168.1.10 --unit 1 --regtype holding --bases 0,40000,50000 --verbose --format json

# List model headers (most-used)
modbusctl client sunspec models --url tcp://192.168.1.10:502 --unit 1
modbusctl client sunspec models --ip 192.168.1.10 --unit 1 --base 40000 --max-models 64 --format json

# Address map view
modbusctl client sunspec map --url tcp://192.168.1.10:502 --unit 1
modbusctl client sunspec map --ip 192.168.1.10 --unit 1 --show-header-regs --compact

# Combined fingerprint + SunSpec summary
modbusctl client sunspec probe --url tcp://192.168.1.10:502 --unit 1
modbusctl client sunspec probe --ip 192.168.1.10 --unit 1 --format json

SunSpec subcommands use the same --format / MODBUSCTL_OUTPUT_FORMAT as other client commands (text default, json, table). A hidden parent flag --json is deprecated and maps to --format json.

Shell completion (install)

Generate and source the completion script for your shell so subcommands and flags (including enum values like --regtype, --algo, --function, --format on client and mcap convert) are completed:

# Bash
source <(modbusctl completion bash)

# Zsh
source <(modbusctl completion zsh)

# Fish
modbusctl completion fish | source

Environment Variable Configuration

Modbusctl supports environment variables for easy automation. The global flag --debug (print debug information) is available on all commands and has no environment variable; use it to enable per-command debug output (e.g. scan: read ranges; read/record: retry wait messages). The environment variables supported (depending on the command) are:

All MODBUSCTL_* environment variables
Variable Type Description Flag Default
MODBUSCTL_ADDRESS uint16 Start address for client read, decode, poll and write (write has no default) --start 1
MODBUSCTL_ALGO string Scan algorithm: safe, smart, deep, stepped, linear, boundary, or sunspec --algo safe
MODBUSCTL_BAUD uint Serial baud rate for rtu:// and ascii:// URLs (0 = 19200) --baud 0
MODBUSCTL_CODEC string Codec ID for client decode, poll and write (e.g. float32/layout:4321, ascii/registers:8, ip_addr) --codec
MODBUSCTL_COUNT uint16 Number of coils/registers to read (with a codec: a multiple of the codec width; 0 = one value) --count 1
MODBUSCTL_DATA_BITS uint Serial data bits, 5–8 (0 = 8 for rtu://, 7 for ascii://) --data-bits 0
MODBUSCTL_DELAY uint16 Delay in ms between client scan requests --delay 0
MODBUSCTL_DURATION uint32 Total duration to record in ms --duration 60000
MODBUSCTL_END uint16 End register address --end 65535
MODBUSCTL_FORMAT string mcap convert output type: csv or json (not client stdout) --format
MODBUSCTL_FUNCTION uint8 Function code (1=coil, 2=discrete, 3=holding, 4=input); client write: 5, 6, 15 or 16 (0 = FC06 for one register, otherwise FC16) --function 3 (write: 0)
MODBUSCTL_INPUT string Input MCAP file (mcap subcommands; server static / server replay) --input
MODBUSCTL_BLOCKS_FILE string JSON address blocks for client record only --blocks-file
MODBUSCTL_INTERFACE string Network interface to use for discovery --interface eth0
MODBUSCTL_INTERVAL uint32 Interval in ms (poll/record/replay iterations or fingerprint probes) --interval 0 (fingerprint), 1000 (poll), 5000 (record/replay)
MODBUSCTL_IP string Modbus TCP device IP address --ip
MODBUSCTL_LOOPS uint16 Number of times to loop the replay --loops 0
MODBUSCTL_OUTPUT string Output MCAP file or directory --output
MODBUSCTL_DATA string Hex-encoded request data for FC08 Diagnostics --data
MODBUSCTL_PARALLEL uint16 Concurrent probes when using identify --unit all (1-64); ignored on serial lines --parallel 10
MODBUSCTL_PARITY string Serial parity: none, even or odd --parity none
MODBUSCTL_POLLS uint32 client poll: number of polls before exiting (0 = until interrupted) --polls 0
MODBUSCTL_PORT uint16 Modbus TCP port or server port --port 502
MODBUSCTL_PROFILE string Device profile to decode --profile
MODBUSCTL_RESOLVE_MAC bool Resolve MAC addresses of discovered devices --resolve-mac false
MODBUSCTL_DISCOVER_FORCE_LARGE bool Allow discover when unique host count exceeds the built-in safety cap --force-large-scan false
MODBUSCTL_SUB_FUNCTION string FC08 Diagnostics sub-function name, lowercase (e.g. returnquerydata, clearcountersanddiagnosticreg) --sub-function returnquerydata
MODBUSCTL_START uint16 Start register address (client scan) --start 1
MODBUSCTL_STOP_BITS uint Serial stop bits, 1 or 2 (0 = 2 without parity, 1 with parity) --stop-bits 0
MODBUSCTL_STEP uint16 Stepped algo: step size (e.g. 100, 1000, 2000) --step 1000
MODBUSCTL_STEP_HALF_OFFSET bool Stepped algo: also probe at step/2 positions --step-half-offset false
MODBUSCTL_RETRY_TIMEOUT uint8 Retry once on timeout/transport (0=no, 1=yes) --retry-timeout 0
MODBUSCTL_SEED_START uint16 Boundary algo: seed start address (known-good read) --seed-start 0
MODBUSCTL_SEED_COUNT uint16 Boundary algo: seed register count (1–125) --seed-count 0
MODBUSCTL_SUNSPEC_BASE uint16 Sunspec algo: known base address (skip detection) --sunspec-base 0
MODBUSCTL_SUNSPEC_BASES string Sunspec algo: comma-separated candidate base addresses --sunspec-bases
MODBUSCTL_SUNSPEC_MAX_MODELS int Sunspec algo: max model headers to read (0=256) --sunspec-max-models 0
MODBUSCTL_SUNSPEC_MAX_SPAN uint16 Sunspec algo: max address span from base (0=no limit) --sunspec-max-span 0
MODBUSCTL_SUBNETS string Subnets to scan for Modbus devices (comma-separated) --subnets
MODBUSCTL_TIMEOUT uint16 Request timeout in ms and dial cap; 0 = 10000 ms default --timeout 0 (most client commands)
MODBUSCTL_UNIT string Unit ID (1-255); for multi-unit commands: single, range (1-10), list (1,5,25), mixed (1-10,255), or all --unit 1
MODBUSCTL_URL string Modbus URL for client commands: tcp://, udp://, rtu://, ascii://, rtuovertcp://, rtuoverudp:// or asciiovertcp:// (e.g. tcp://192.168.1.10:502, rtu:///dev/ttyUSB0); mutually exclusive with --ip/--port --url
MODBUSCTL_VALUES string client write: comma-separated values to write --values
MODBUSCTL_REGTYPE string Register type for sunspec: holding or input --regtype holding
MODBUSCTL_SUNSPEC_BASES string Comma-separated base addresses to probe (sunspec detect) --bases 0,40000,50000,…
MODBUSCTL_SUNSPEC_BASE uint16 Known SunSpec base address; skip detection when set (sunspec models/map) --base 0
MODBUSCTL_SUNSPEC_MAX_MODELS int Maximum model headers to read; 0 = 256 (sunspec models) --max-models 0
MODBUSCTL_SUNSPEC_MAX_SPAN uint16 Maximum address span from base; 0 = no limit (sunspec models) --max-address-span 0
MODBUSCTL_VERBOSE bool Show probe attempts or extra detail (e.g. sunspec detect) --verbose false
MODBUSCTL_OUTPUT_FORMAT string Client stdout format: text, json, or table (identify, read, decode, write, poll, scan, record, reportserverid, fingerprint, diagnostic, sunspec, …). Empty/unset defaults to text. Not used by mcap convert (see MODBUSCTL_FORMAT). --format text

Example usage:

MODBUSCTL_IP=192.168.1.10 MODBUSCTL_ADDRESS=40001 MODBUSCTL_COUNT=10 modbusctl client read
MODBUSCTL_URL=rtu:///dev/ttyUSB0 MODBUSCTL_BAUD=9600 MODBUSCTL_PARITY=even MODBUSCTL_UNIT=3 modbusctl client poll --start 0 --count 4
MODBUSCTL_IP=192.168.1.10 MODBUSCTL_ALGO=smart MODBUSCTL_START=0 MODBUSCTL_END=1000 MODBUSCTL_OUTPUT=scan.mcap modbusctl client scan

FAQ

What is modbusctl?

modbusctl is a command-line tool for Modbus over TCP, UDP and serial lines (RTU and ASCII). It reads, polls and writes coils and registers, identifies devices, fingerprints supported function codes, scans register maps, decodes registers into typed values, discovers devices on a network, and records and replays sessions to simulate devices.

How do I find which Modbus registers a device exposes?

Run a scan, for example modbusctl client scan --ip 192.168.1.10 --algo smart --start 0 --end 5000 --output scan.mcap. Use --algo safe with --delay for fragile devices and --algo deep for precise block edges. See Scan registers.

How do I read a float or string from Modbus registers on the command line?

Use client decode with a codec, for example modbusctl client decode --ip 192.168.1.10 --start 40001 --codec float32/layout:4321. List all codecs with modbusctl client codecs. See Decode registers.

How do I simulate a Modbus device without hardware?

Record or scan a real device to an MCAP file, then serve it with modbusctl server static --input session.mcap --port 1502 (fixed values) or modbusctl server replay --input session.mcap (values replayed over time).

Does modbusctl support Modbus RTU (serial)?

Yes. Pass a serial URL to any client command, for example modbusctl client read --url rtu:///dev/ttyUSB0 --baud 9600 --parity even --unit 3 --start 0 --count 4. Modbus ASCII (ascii://), Modbus UDP (udp://) and RTU or ASCII through a serial-to-Ethernet bridge (rtuovertcp://, asciiovertcp://) work the same way. See Transports and serial settings.

Can modbusctl write registers or coils?

Yes. modbusctl client write --ip 192.168.1.10 --start 100 --values 1234 writes a holding register; --function 5 or 15 writes coils, and --codec writes typed values such as floats. See Write coils and registers.

How do I poll Modbus registers continuously?

Use modbusctl client poll --ip 192.168.1.10 --start 100 --count 4 --interval 1000. It prints a sample per poll until you press Ctrl-C (or after --polls samples), with --format json for one JSON object per line. See Poll registers continuously.

My serial device does not answer. What should I check?

The serial settings must match the device exactly: --baud, --parity, --stop-bits and --data-bits. Many devices use 9600 8N1 (--baud 9600 --parity none --stop-bits 1), while modbusctl defaults to 19200 with no parity and 2 stop bits. Also check the --unit ID, that A/B are not swapped on RS-485, and whether the device speaks RTU (rtu://) or ASCII (ascii://).

What is MCAP?

MCAP (Modbus Capture) is a compact capture format, inspired by PCAP, that stores Modbus transactions with timestamps for replay and analysis. See MCAP format.

How do I use modbusctl in scripts and CI?

Pass --format json (or set MODBUSCTL_OUTPUT_FORMAT=json). Progress goes to stderr, a single result goes to stdout, and failures return one JSON error object with a stable exit code. See General CLI usage and docs/exitcodes.md.

How is modbusctl different from mbpoll and modpoll?

mbpoll and modpoll are polling and writing tools. modbusctl polls and writes too, and adds register-map scanning, device identification, SunSpec discovery, subnet discovery and record/replay simulation. See the comparison.


Project structure

Repository layout
modbusctl/
├── cmd/
│   ├── client (Identify, Fingerprint, Diagnostic, ReportServerID, Read, Decode, Poll, Write, Record, Scan, SunSpec commands)
│   ├── discover (Device discovery)
│   ├── mcap (MCAP file operations: convert, decode, extract, frequencies, info, strings)
│   └── server (Modbus TCP data replay server)
├── internal/
│   ├── config (CLI & env: types, flags, completion, diagnostics, Modbus URL / SunSpec base parsing)
│   ├── cli (shared Cobra helpers: enum completion, stdout file, required flags, debug)
│   ├── format (client stdout **text/json/table** via `Write`, streaming output via `StreamWriter`; MCAP-derived **strings** / **frequencies** heuristics; table rendering)
│   ├── mcap (MCAP binary codec, load, CSV/JSON/blocks/info exports, profile decode)
│   ├── runner (client command wiring, formatted run loop, fatal JSON/text rendering)
│   ├── errs (typed CLI errors, stable codes, exit-kind mapping)
│   ├── mbtest (in-memory Modbus device for tests: TCP, UDP, RTU/ASCII over TCP and on a pseudo-terminal)
│   ├── modbus (Modbus client/server logic, collectors, poll and write, scan strategies)
│   ├── types (DTOs for JSON/text/table output and MCAP-related structs)
│   └── validate (Input validation and checks)
├── Makefile (Build & test commands)
└── go.mod (Dependencies)

Development

A toplevel Makefile is provided for convenience. Run make (or make help) for the full list. Common targets:

Target Purpose
make test Unit tests with race detector (go test -race ./...)
make coverage Tests + coverage.out across the whole module; fails below 85% total statement coverage (COVERAGE_MIN)
make compile Full-module typecheck (go build ./...)
make lint compile then staticcheck
make lint-ci compile, go vet, golangci-lint (uses .golangci.yml)
make fmt / fmt-check Format with the gofmt of the Go version in go.mod (the one CI uses); fmt-check fails if that gofmt or the locally installed one would change any file
make check fmt, fmt-check, lint, lint-ci, vet, test, coverage
make build Runs check then writes bin/modbusctl
make build-all / release-all Cross-compile and package archives

Building

make build writes the binary to bin/modbusctl (not the repo root).

make build
make build-all

Running Tests

make test
make coverage

Tests need no hardware: internal/mbtest provides an in-memory Modbus device that is served over TCP, UDP, RTU/ASCII framing over TCP, and RTU/ASCII on a pseudo-terminal that stands in for a serial port (Linux and macOS; those tests are skipped elsewhere).

Version History

Release notes for each version are maintained in RELEASE.md (e.g. migration notes and breaking changes).


Contributing

Bug reports, device-compatibility notes and pull requests are welcome. Please open an issue to discuss larger changes first, and run make check before submitting. See CONTRIBUTING.md for the development setup and guidelines.

Please report security vulnerabilities privately, as described in SECURITY.md, not in a public issue.

If modbusctl is useful to you, a star on GitHub helps other engineers find it.


License